VRF MAINTENANCE AND REPAIR

The regular AC service important to keep your HVAC system in working reliabil condition for the long time and to prevent any potencial breakdowns and keep system afficiant. As your air conditioner recicle the air in your house and you breath this air, it is important to keep it clean for your personal health.

To void a faild of your air conditioner at most critical moment keep service of air conditioner regulary. All work performed by Good Air covered by warranty for 30 days. By dealing with us you can be sure that AC service done properly.

ENTER YOUR NUMBER AND WE WILL CALL YOU WITHING 10 MINUTS



TROUBLESHOOTING AND REPAIRING OF VRF SYSTEMS


Good Air as a company that specialises in HVAC maintennace, offering trouble shooting and repairing services for ‘problem’ air conditioning systems, we see with the many different and bespoke air conditioning systems installed.

A disturbing trait is emerging where VRF systems show signs of trouble, in that when things go wrong, they tend to go from bad to worse over relatively short timeframes and can render complete systems unusable well before expectations. Trust your HVAC maintenance and repair to professionals.


VRF TROUBLESHOOTING:

Most of the VRF system has self trouble analysis function, and when system in error status, the outdoor unit or indoor unit can display the error code. The difficults is that the same error can be cause of diffirent reasons and here VRF repairing should be as per desision of HVAC technician. Somitimes the system does not showing any error, but VRF not working properly. Here It requirs some special equipment and tools to reqtify the problem.


Tipical problems with VRF system
  • The complex nature of VRF systems can result in many different problems. Electronic equipment, electrical, electronic and control component failures.
  • Controls component failures can be exacerbated by vibration from fans & compressors, exposure to excessive temperatures and poor quality power supplies.
  • The most common ‘serious’ problem for a VRF system is a compressor failure. Compressor failures are generally classified: as electrical - compressor motor failure and as mechanical compressor failure. The most common cause of an electrical (or compressor motor) failure is from the systems oil becoming acidic.
  • Acidic oil - The oil can become acidic due to undiagnosed leaks, poor installation / workmanship & previous compressor failures). The acidic oil eats away the electrical insulation on the motor and causes an electrical ‘short’.
  • Refrigeration system blockage - The most common cause of a mechanical (compressor) failure is a lack of oil, usually caused by sludge and blocked strainers and oil-ways within the machine.

If VRF repairs, such as a compressor or other refrigeration component replacement is required or remedial work such as relocation of an indoor unit is required; all of the measures relating to a new installation will be required – there are no shortcuts without consequences.

  • VRF Pressure test
  • Deep vacuuming
  • Correct refrigerant charge

One significant difference from new build installations is that there is likely to be significantly more pressure to get the system back up and running due to the building occupants complaining of no air conditioning. Thats why it very important to have qualified technicians and professional VRF repairing tools to comleate all repairing works within minimized time frame.



VRF MAINTENANCE


Variable Refrigerant Flow (VRF) systems maintenance are one of the most difficult. A disturbing trait is emerging where VRF systems show signs of trouble, in that when things go wrong, they tend to go from bad to worse over relatively short timeframes and can render complete systems unusable well before expectations. It is heighlyy important to maintenance VRF system by professionals.

VRF MAINTENANCE

Given that these systems are relatively expensive and the cost and disruption associated with early replacement is very high we advice to trust your VRF installation, maintenance and repairing to professionals.

Whats going wrong in VRF maintenance:

Given that these systems are relatively expensive and the cost and disruption associated with early replacement is very high we advice to trust your VRF installation, maintenance and repairing to professionals.

There are several areas we see as possible contributors to early failure: Obsolescence of VRF system

Some of the earlier VRF systems introduced 10-15 years ago are now effectively obsolete, with parts being increasingly expensive and difficult to source. Where parts are unavailable or expensive and the system is reliant on R22 refrigerant, the point of no return is quickly reached, leaving the only viable option for the building owner to replace the system.

Poor installation of VRF system

Refrigerant leaks, improper evacuation, poor or no pressure testing and the lack of nitrogen purging during pipework welding can all result in premature failure of the systems.

Poor maintenance of VRF system

Some of the contributing factors are:

It is very difficult to determine if refrigerant levels are correct by simply connecting refrigerant pressure gauges, due to the widely varying operational states that can exist as the indoor units all behave independently. Where a loss of refrigerant has been detected, the only sure way to re-charge the system with the correct volume of refrigerant is to decant all of the refrigerant out of the system and replace it with a known (weighed) quantity. Time and cost pressures often mitigate against this practice.

The right people

VRF systems are complex and requiring very high standards of design, installation and maintenance. Professional vrf maintenance companies may be more expensive than typical service providers, but these costs fade into insignificance compared with the costs attached to premature system failure.

The critical factors towards getting most out of your VRF Maintenance are:

If the above guidelines are followed, we remain optimistic that a life expectancy in excess of 12-15 years could be achieved.



VRF COMISSIONING


PRESSURE TEST
For all VRF sytem commissioning for pressure test we will following this algoritm:
  • first achive pressure for 150 PSIG and held for 3 minutes;
  • second, increase pressure for 325 PSIG and hold for 5 minuts;
  • Third, if no leaks detected, increase pressure to 550 PSIG and hold for 24 hours.
VACUUMING OF SYTEM
A triple evacuation of all piping should be performed to eliminate moisture in the system. For VRF sytem commissioning the vacuuming of system as per following algoritm:
  • Vacuum the system to 4000 microns, hold 15 min., break vacuum with nitrogen to a pressure 5 PSI for 5 minuts
  • Vacuum the system to 1500 microns and hold for 20 minutes.
  • Vacuum the system to not more then 500 microns and hold for 1 hour.
Why is a triple evacuation so important instead of a deep vacuum? The reason lies in the relationship between pressure and temperature with water. When the first vacuum is pulled, some of the moisture in the lines boils and evaporates. However, once it reaches a certain pressure the water will actually freeze and leave small ice crystals in the system. This is why a single deep vacuum is insufficient.